Study analyzes effectiveness of reflective ceilings

Study analyzes effectiveness of reflective ceilings

Engineers at Brinjac quantify the illuminance and energy consumption levels achieved by increasing the ceiling’s light reflectance.


By C.C. Sullivan and Barbara Horwitz-Bennett | September 16, 2013
To quantify the illuminance and energy consumption levels achieved by increasing the ceiling’s light reflectance (LR), ceiling system manufacturer Armstrong World Industries commissioned Brinjac Engineering to conduct two controlled studies. (Illuminance is a measure of the intensity of light on a unit area of a surface.)
 
In the first study, four different room configurations were outfitted with a direct recessed 2X2-foot parabolic troffer and an indirect pendant. One set of rooms was given a 75% reflective ceiling; the others, a 90% reflective ceiling. After measuring work plane illuminance in both sets of rooms, Brinjac found the 0.90 LR ceiling to increase direct lighting levels by just 2–5%; however, indirect lighting levels jumped by almost 22% and offered greater lighting uniformity.
 
Although work plane illuminance from direct lighting only increased modestly when changing the light reflectance from 0.75 to 0.90, the effect of indirect lighting on work plane illuminance was significant. In addition, the higher LR value enabled a reduction in indirect luminaire fixtures and a decrease in lighting power density.
 
Based on these results, specifiers can use fewer fixtures or lower wattage levels to achieve required lighting levels, which can reduce energy costs, as analyzed in the second study where the 90% reflective ceiling tile was installed in the same spaces with an optimized lighting design and compared to the 75% and 90% ceiling with the original lighting scheme.
 
After comparing the three ceiling designs, the Brinjac researchers found that:
• Spacing between indirect luminaire sections with the 0.90 ceiling could be increased, thereby reducing the total number of luminaires required to achieve light levels afforded by the 0.75 ceiling.
• The 0.90 reflective ceiling with indirect fixtures yielded a 23% lower lighting power density than the 0.75 ceiling, and 21% lower than the parabolic troffer layout.
• This lighting power density reduction was calculated to achieve 9% HVAC energy costs savings, as compared to the 0.75 ceiling, and 7% in relation to the troffer layout.
 
For more information on this study, see: http://www.armstrong.com/common/c2002/content/files/38652.pdf. 

Related Stories

| Apr 3, 2012

Product Solutions

Two new PV systems; a lighter shelf; and fire alarm/emergency communication system.

| Apr 3, 2012

SSOE acquires MEP Firm CRS Engineering & Design Consultants

The acquisition will expand SSOE’s Southeastern U.S. presence, broaden CRS’s reach to international markets, and provide both firms’ clients access to enhanced services and resources.

| Apr 2, 2012

Mitsubishi unveils ultra-high-speed elevator for Shanghai skyscraper

The operation of the elevator is scheduled to begin in 2014.

| Mar 30, 2012

18 handy tablet apps for AEC professionals

Check out these helpful apps for everyday design and construction tasks. Our favorite: MagicPlan, which uses GPS to help you measure and draw a floor plan of any room.

| Mar 29, 2012

Construction completed on Las Vegas’ newest performing arts center

The Smith Center will be the first major multi-purpose performance center in the U.S. to earn Silver LEED certification.

| Mar 27, 2012

Skanska hires aviation construction expert Bob Postma

Postma will manage Skanska’s nationwide in-house team of airport construction experts who lead the industry in building and renovating airport facilities and their essential features.

| Mar 21, 2012

10 common data center surprises

Technologies and best practices provide path for better preparation.

| Mar 20, 2012

New office designs at San Diego’s Sunroad Corporate Center

Traditional office space being transformed into a modern work environment, complete with private offices, high-tech conference rooms, a break room, and an art gallery, as well as standard facilities and amenities.

| Mar 16, 2012

Work on Oxnard, Calif. shopping center resumes after a three-year hiatus

Stalled since 2009, developers of the Collection at RiverPark decided to restart construction on the outdoor mall. 

| Mar 13, 2012

China's high-speed building boom

A 30-story hotel in Changsha went up in two weeks. Some question the safety in that, but the builder defends its methods.

boombox1 - default
boombox2 -
native1 -

More In Category

AEC Tech

Lack of organizational readiness is biggest hurdle to artificial intelligence adoption

Managers of companies in the industrial sector, including construction, have bought the hype of artificial intelligence (AI) as a transformative technology, but their organizations are not ready to realize its promise, according to research from IFS, a global cloud enterprise software company. An IFS survey of 1,700 senior decision-makers found that 84% of executives anticipate massive organizational benefits from AI. 




halfpage1 -

Most Popular Content

  1. 2021 Giants 400 Report
  2. Top 150 Architecture Firms for 2019
  3. 13 projects that represent the future of affordable housing
  4. Sagrada Familia completion date pushed back due to coronavirus
  5. Top 160 Architecture Firms 2021