flexiblefullpage -
billboard - default
interstitial1 - interstitial
catfish1 - bottom
Currently Reading

Moisture design tips for ice rinks

Moisture design tips for ice rinks

Specialty Buildings Column Series, Part 4 of 6


By Sean O'Brien, PE, LEED AP, Simpson Gumpertz & Heger | August 11, 2010
Photo: www.ballerhouse.com                       
                 
               

Ice rinks present several unique challenges for designers, all stemming from the fact that the floor of the rink is maintained at below-freezing temperatures while the remainder of the building is kept much warmer. 

Interior temperature and relative humidity levels in ice rinks can vary
       
This special report is the fourth installment of a six-part series from Sean O'Brien on moisture-related design for specialty buildings. 

The series includes:
Indoor swimming pools/natatoriums
Museums and archives
Hospitals
Ice rinks
Cold storage facilities
Indoor ski parks 
     
widely, as many ice rinks are not intentionally heated or cooled, and may or may not be ventilated. While the problems often encountered in ice rinks are generally less catastrophic than those found in humidified buildings (with one primary exception, discussed below), they can still have a negative impact on the occupants of the building.
TYPES OF ICE RINKS
There are three primary types of ice rinks: conditioned, partially conditioned, and unconditioned. These loosely correspond to three primary construction types: fully enclosed, partially enclosed, and open. 

Depending on the type of building enclosure, the ice surface may be kept frozen either by a matrix of cooling pipes in the slab below the ice (in the case of fully enclosed rinks) or via natural low temperatures during the winter months (more typical of open rinks).

A fully enclosed ice rink is likely to have insulated walls and roofs, as well as mechanical systems that are capable of both heating and cooling. Fully enclosed ice rinks are also more likely to have some type of ventilation and dehumidification capabilities, allowing for tighter control over interior conditions. This control is especially necessary in venues such as professional hockey arenas that draw large crowds of spectators. Without adequate mechanical systems, the thermal and moisture loads from building occupants would be unmanageable, leading to high interior temperature and relative humidity levels.

The interior conditions and design of the mechanical system must be balanced with the refrigeration system for the ice surface, as heat added to the space will eventually need to be taken out by the refrigeration system to maintain the ice at the desired temperature.

Partially enclosed ice rinks may have a complete building enclosure in the sense of having four walls and a roof, but may not be insulated or contain open or louvered wall areas.
            
Ice rink design guidelines

The following must be considered when designing ice rinks:
• Design building mechanical systems with heating, cooling, and dehumidification capacities based on accurate building enclosure performance criteria, occupant load estimates, and seasonal operating schedule. 

• Coordination between mechanical engineers and building designers is critical to achieving a successful, integrated design.

• Establish the intended operating schedule for the building (e.g., year-round, winter only, etc.) to assess the likelihood of condensation and frost heave problems.

• Evaluate the risk of frost heave by determining the susceptibility of the local soils and the depth of frost penetration below the slab.
Where appropriate, design heating pipes or a ventilated crawlspace to prevent frost heaving below the ice surface.

• Evaluate the need for low-emissivity materials/coatings for building components above the ice surface based on ice temperature and expected interior relative humidity levels.
            
The lack of a thermally efficient and moderately airtight building enclosure in partially enclosed rinks makes a traditional mechanical system unfeasible. These types of spaces often have discrete unit heaters or no heaters at all, and may be ventilated directly with outside air. This provides some ability to reduce interior temperature and moisture levels during cold weather, but does not provide the same level of control as a complete mechanical system.
In addition, summer operation of these types of ice rinks is generally not possible due to the inability to cool or dehumidify the interior air.  In many climates, operation during “swing seasons” (i.e., fall and summer) may also be problematic due to the incidence of high exterior moisture levels combined with moderate temperatures. For example, ventilating an ice rink to control temperature on a cool, moist fall day could have the side effect of increasing interior humidity levels.

Lastly, many ice rinks consist of an ice surface with an open-walled roof structure or pavilion to protect the ice from rain or snow. The lack of any real enclosure prevents any heating or cooling of the space around the ice, although infrared heaters may be used for localized occupant comfort. 

CONDENSATION ISSUES
When designers think of condensation problems in buildings, the sight of water dripping from window frames or skylights often comes to mind. In ice rinks, condensation manifests itself somewhat differently, often to the surprise of architects and engineers.

The first condensation problem found in ice rinks occurs due to a combination of high relative humidity levels, low surface temperatures on the ice, and stagnant air near the ice surface.  Since the ice temperature will also determine its hardness, the ideal ice surface temperature depends on the use of the facility (i.e., competitive hockey, recreational skating, etc.) at a given point in time. Typical ice surface temperatures range from approximately 22°F to 28°F.

Under the right circumstances, moisture in the interior air may begin to condense just above the surface of the ice, not unlike the formation of clouds in pockets of cold air. This produces a blanket of fog over the ice surface. Although not necessarily detrimental to the building itself, heavy fogging can render an ice rink facility unusable for its intended purpose. A famous example of fogging is the old Boston Garden, where dense fog over the ice made for interesting play and angry fans during the playoffs.

A properly designed mechanical system is the key to preventing fogging near the ice by providing humidity control and possibly air circulation near the ice surface. Such a system must be designed to consider both prevention of condensation and energy efficiency, as excessive airflow over the ice may create unnecessary loads on the refrigeration system. 

The second condensation problem can occur far from the ice surface, but still directly above it.  Objects in a building will always radiate heat to surfaces at lower temperatures. Since the ice surface is generally the coldest surface in the building, nearly all surfaces in the building will radiate heat to the ice surface, reducing their surface temperatures (Figure 1).
          
             

Figure 1. Heat loss from warm ceiling to ice rink surface
              
          

This cooling effect is greatest on components with direct line of sight to the ice, typically the roof construction. The cooling effect of the ice will vary depending on the amount of roof insulation as well as the interior temperature, but can reduce surface temperatures by 10°F or higher. If combined with high enough interior humidity, undercooling of the ceiling structure can cause condensation, resulting in water dripping onto the ice surface. Dripping water can quickly create bumps and irregularities on the ice surface that may pose a hazard to skaters and a nuisance to spectators.

Condensation control can be achieved in two ways. The first is to maintain interior relative humidity levels below the condensation threshold. This is a feasible solution only in buildings with capable mechanical systems, and is generally not an option for open or partially enclosed rinks.

The second is maintaining interior surface temperatures of the building enclosure above the dew point temperature of interior air by reducing radiative heat transfer to the ice. This can be accomplished by using low-emissivity paints or barriers on or below the ceiling structure. Foil barriers are typically more effective, but less aesthetically pleasing, than applied coatings (Photo 1). 
           
            

Photo 1. Low-emissivity barrier (foil sheet) used to reduce heat loss from ice rink ceiling        
          
   

Just as low-emissivity, or “low-e,” coatings on insulating glass units can reduce heat gains due to solar radiation, they can be used to reduce radiation from ceiling structures to the cold ice surface below (Figure 2). The type of low-e product used will depend on the potential severity of the condensation problem and the expected interior humidity levels. Another benefit of low-e ceilings is that, by reducing radiative heat transfer from the ceiling (often the underside of the roof) to the ice surface, the refrigeration load for the ice surface will be reduced 
      
        

Figure 2. Heat loss to ice surface reduced with low-emissivity coating (green dotted line)          
         
       

FROST HEAVE
In addition to creating condensation problems, the frozen ice surface can create problems below the building. In a typical heated or partially conditioned building, the ground below the occupied space is kept relatively warm (i.e., above freezing) by heat loss from the interior space. This is true even in buildings with insulated floor slabs (Figures 3 and 4). 
          
               

          
Figure 3. Temperature profile and frost line below heat building with uninsulated slab
          

Figure 4. Temperature profile and frost line below heat building with R-10 insulated slab
            
        

In an ice rink, where the slab surface is below freezing, no such soil heating occurs and the ground below the building may freeze (Figure 5). Depending on the local soil and groundwater conditions, and the ice rink’s operating seasons, frost heave may occur in the soil below the rink surface. 

         
             

Figure 5. Temperature profile and frost line below ice rink
          
         

The exact mechanisms of frost heave are complex, but the essential process is simple: As water accumulates and freezes in the soil, the resulting volumetric expansion (approximately 9%) “pushes” or exerts an upwards force on the slab (Figure 6). Heaving soils can exert sufficient pressure on the slab to cause cracking and displacement. Such damage could render the rink unusable and require costly repairs, especially if the cooling matrix for the ice is damaged. This is in contrast to the problems previously discussed, which affect the operation of the building but not the building itself. 
         
          

Figure 6. Schematic diagram of frost heave below ice rink
         
          

Sub-slab insulation alone may not be sufficient or may need to be installed in thicknesses too large to be practical in preventing frost heave. Some type of supplemental heating, such as heating pipes or cables, is often necessary to prevent long-term freezing of the ground below the rink surface.

An alternative, though somewhat more complex, is to create a crawlspace between the ice and the ground and to ventilate that space with heated air. It should be noted that frost heave is less likely occur if an ice rink operates for only part of the year, as seasonal thawing of the ground may prevent long-term ice accumulation. The seasonal use of the building and the associated risk of frost heave must be evaluated during the design process.


Sean O’Brien is a Senior Project Manager in the New York City office of Boston-based Simpson Gumpertz & Heger Inc. O’Brien specializes in building science and building envelope performance, including computer simulation of heat, air, and moisture migration issues. He has investigated and designed repairs for a variety of buildings types, from condominiums to art museums, and has published papers on topics including moisture migration in masonry wall systems and condensation resistance of windows and curtain walls. He can be reached at smobrien@sgh.com.

boombox1 - default
boombox2 -
native1 -
halfpage1 -

Most Popular Content

  1. 2021 Giants 400 Report
  2. Top 150 Architecture Firms for 2019
  3. 13 projects that represent the future of affordable housing
  4. Sagrada Familia completion date pushed back due to coronavirus
  5. Top 160 Architecture Firms 2021