The risks of mismatched fire-rated assemblies

Mismatched fire-rated glass and framing happens more often than you think. Failing to confirm that the tested and listed performance capabilities of the framing system match those of the glazing can create a financial nightmare for the entire building team. 

April 01, 2014 |
Bill O'Keeffe

Mismatched fire-rated glass and framing happens more often than you think. Failing to confirm that the tested and listed performance capabilities of the framing system match those of the glazing can create a financial nightmare for the entire building team. 

In simple terms, the entire assembly must fully meet the requirements of the code. 

Seems straightforward enough. 

So why are fire protective hollow metal frames used in stairwell enclosures, fire barriers or other applications where fire resistive assemblies (both glass and frames) are required?  

Here are a few reasons behind the confusion, and how costly mistakes can be avoided.

 

1. Standard hollow metal frames cannot be used in many 60- and 90-minute applications. 

Like fire-rated glass, fire-rated framing must be listed with a nationally recognized testing laboratory (such as UL and Intertek/Warnock-Hersey) to confirm that it was tested to a particular standard; it does not confirm code compliance. Hollow metal is listed up to 90 minutes, but cannot be used in many 60- and 90-minute applications because it doesn’t meet ASTM E-119, which is usually required in applications over 45 minutes because of radiant heat concerns.

 

2. Many are confused about what constitutes an “assembly.”  

For walls and window openings, it’s clear that the complete assembly means both the glass and frames. But when it comes to door assemblies, it can be less apparent. NFPA 80 defines door assemblies as a combination of the door, frames, hardware, sidelites and transoms. The IBC also makes it clear that sidelites, transoms and frames are part of the door assembly. This means that both the glass and the frames must meet the required testing for the application. Using fire protective framing, like hollow metal, with fire resistive glass voids the fire resistive rating of the assembly.

 

3. Sidelite/transom and interior window applications using hollow metal frames over 45 minutes are limited.  

The hollow metal frames cannot be used in 60 and 90 minute door assemblies that include sidelites and transoms, such as the ones found in 1-2 hour exit enclosures, stairwells and fire barrier walls, where fire resistive glazing ASTM E119 is permitted when tested as an assembly meeting ASTM E119. In 1 hour exit corridors, 45 minute openings that exceed 25 percent of the wall area must be fire resistive and equal to the rating of the wall. The framing must also be fire resistive, once again limiting the use of hollow metal frames. 

 

4. Misconceptions when sprinklers are present.

What effect, if any, do sprinklers have on code requirements for fire-rated assemblies? In particular, what do the codes say about glass and framing used in 60 and 90 minute door assemblies in exit passageways and exit enclosures? Although temperature rise doors may not be required in these applications where the building is fully sprinklered, fire protective glazing in 60 and 90 minute door vision panels are limited to 100 sq. in. due to radiant heat concerns. 

Today’s fire rated framing systems have outperformed standard hollow metal frames in many ways – higher fire ratings that meet ASTM E-119, increased design options and finishes, even make-ups that protect against hurricanes, bullets and blast. Knowledge of building codes, allowed applications and product performance opens up a world of possibilities for designers.

Read the complete article on the SAFTI FIRST website. 

Editor's note: This is sponsored content. The text was provided by the sponsored company.

Bill O'Keeffe | Clear on Technical Glass
SAFTI FIRST Fire Rated Glazing Solutions

About the Author: Bill O’Keeffe is the President and CEO of SAFTI FIRST Fire Rated Glazing Solutions, a leading USA-manufacturer of advanced fire rated glass and framing systems.  An industry veteran and innovator with over 45 years of experience in architectural glazing, he was first to introduce and manufacture clear, fire resistive glazing products in the US.  He is also a safety advocate who exposed the dangers of traditional wired glass, which lead to code changes and fire rated glass products that are safe, affordable and clear alternatives to traditional wired glass.  Today, Bill continues to develop building products that enable architects to create beautiful, safe and energy-efficient spaces with advanced glazing systems.

Related Blogs

October 25, 2017 | Fire-Rated Products | Clear on Technical Glass

To avoid confusion, we are proposing separate charts for fire protective and fire resistive products.

Fire protective glazing used in a door vision panel in 60-90 minute exit stairway

The 2012 and 2015 IBC limits the size of ceramics and fire protective glazing used in the door vision panel in 60-90 minute exit stairway or passageways to 100 sq. in. regardless if the building is fully sprinklered. The only way to exceed the 100 sq. in. vision panel limitation is by using fire resistive glazing that meets ASTM E-119. 

July 19, 2017 | Fire-Rated Products | Clear on Technical Glass

As shocking as the Grenfell Tower fire was, it is not an isolated incident.

June 13, 2017 | Fire-Rated Products | Clear on Technical Glass

The ASTM E-119 test is the most stringent and most difficult test to pass for all fire rated glazing assemb...

GPX Hurricane with FL Product Approval was used in the new VA Medical Center in Orlando, FL.  Architect: RLF Architects.  Glazier: Harmon Inc. Photo Credit:  SAFTI FIRST

March 22, 2017 | Fire-Rated Products | Clear on Technical Glass

It may look like a regular window, but these advanced fire resistive glazing systems are recognized in the...

January 03, 2017 | Glass and Glazing | Clear on Technical Glass

Our mission is to produce appealing architectural products that protect people while providing our customer...

November 10, 2016 | Fire-Rated Products | Clear on Technical Glass

SuperLite II-XLM is a fire resistive multi-laminate glass product that meets ASTM E-119/UL 263/NFPA 251 and...

Photo: Messe Düsseldorf/ctillmann

October 14, 2016 | Glass and Glazing | Clear on Technical Glass

With 9 exhibition halls showcasing over 1,235 exhibitors from 52 countries and with over 40,000 visitors fr...

August 25, 2016 | Fire-Rated Products | Clear on Technical Glass

Choosing the correct and code approved fire rated glazing product can be confusing, this FAQ can help.

On New York City’s bulletin on lot line requirements – and how it applies everywhere else

1 hour curtain wall adjacent to a parking area in a private office in Valley Stream, NY. Products used: SuperLite II-XL 60 with PPG Starphire Low-Iron insulated with Low-E in GPX Curtain Wall Framing; Architect: RPF; Glazier: AMG Contracting

May 06, 2016 | Fire-Rated Products | Clear on Technical Glass

Determining when fire rated requirements apply, the type of fire rated glazing allowed, how much fire rated...

Overlay Init