Unless the design and construction techniques include a continuous air barrier system, it is.
BASF Polyurethane Foam Enterprises LLC
July 7, 2006
Building Design and Construction
It’s quite literal. The building draws unconditioned air in, then leaks conditioned air back out through holes, cracks, gaps and other leaks of varying size. It’s called “uncontrolled” air leakage, and it costs a lot of money. The United States Department of Energy estimates uncontrolled air leakage can account for 30 percent or more of a building’s heating and cooling costs, and contribute to problems with moisture[i].
Most industrial, commercial and institutional buildings in the United States leak air. It is not the HVAC engineer’s fault. You can design the most efficient HVAC system imaginable, and the building will still draw in air. However, a simple understanding of the interaction between the HVAC and the building envelope can help you prevent future buildings from drawing air in and leaking air out with the inclusion of a continuous air barrier system. Here’s how it works…
Air leakage occurs through cracks, gaps, holes, pores in materials and other openings in the building envelope. Air flow is the result of pressure differences. When air leaks, it takes with it heat, water vapor, smoke, pollutants, dust, odors, allergens and anything else it can find and carry. Energy moves from regions of high to regions of lesser potential: hot and cold, high pressure to low, and so on.
There are three major sources of pressure that cause air to leak: wind pressure, stack pressure and HVAC fan pressure. Of the three, wind is usually the greatest. When averaged out over the course of a year, it is about 10-15 mph (0.2-0.3psf or 10-14Pa) in most locations in North America[ii]. If it hits the building straight on, air enters the envelope on the windward side and exits on the other three sides and at the top, through the roof. If the wind hits at an angle, air exits the building on the two leeward sides and the roof.
Stack effect, also sometimes referred to as chimney effect, is caused by buoyancy or the simple physics lesson that hot air rises. The weight of the column of conditioned air inside the building compared with that outside creates a pressure difference across the building envelope. The taller the building is, the greater the stack pressure will be. Warm, conditioned air escapes through holes at the top of the building and at the roof. The resulting lower pressure at the bottom of the building draws in air from the surrounding environment.
The third pressure comes from the mechanical system itself. Mechanical engineers and on-site managers often choose to bring in makeup air to increase pressure and overcome the infiltration at the base of the building. Unfortunately, this increases pressure at the top, causing more exfiltration problems in that area.
How does an air barrier system increase energy efficiency?
When uncontrolled air leakage occurs, the HVAC system has to work harder to maintain the indoor environment. An effective air barrier system, quite simply, controls air movement into and out of the building. This allows the HVAC system to do its job uncompromised by having to make up for a disproportionately large amount of the air it is conditioning leaving the building.
And of course, increasing the operating efficiency of the HVAC system reduces energy consumption and, therefore, operating costs. In fact, the inclusion of an effective air barrier system may allow the HVAC system to be downsized at the design stage – in some cases by a substantial amount.
“Despite common assumptions that envelope air leakage is not significant in office and other commercial buildings, measurements have shown that these buildings are subject to larger infiltration rates than commonly believed. Infiltration in commercial buildings can have many negative consequences, including reduced thermal comfort, interference with the proper operation of mechanical ventilation systems, degraded indoor air quality, moisture damage of building envelope components and increased energy consumption.”
-Excerpt from the 2005 National Institute of Standards and Technology (NIST) report, Investigation of the Impact of Commercial Building Envelope Airtightness on HVAC Energy Use.
According to the National Institute of Standards and Technology (NIST) report, Investigation of the Impact of Commercial Building Envelope Airtightness on HVAC Energy Use, the inclusion of an air barrier system in four sampled types and sizes of building can reduce air leakage by up to 83 percent. This represents a large reduction in current and future energy consumption and operating costs: potential gas savings of greater than 40 percent, and electrical savings of greater than 25 percent.
The study evaluated the energy savings of an effective air barrier requirement for non-residential buildings in five cities representing different climate zones. The methodology included blended national average heating and cooling energy prices and cost effectiveness calculations matching the scalar ratio employed by ASHRAE SSPC 90.1. Energy simulations were performed using TRNSYS (Klein 2000). Simulations of annual energy use were run using TMY2 files (Marion and Urban 1995).
The research team selected whole building airtightness levels that were judged to be readily achievable and used these as the whole building target used in the energy modeling. The baseline buildings used in the comparison were modeled with leakage levels based on a database of commercial building leakage measurements.
Let’s look at one of the building models used in the study: the office building.
The model was a two story office building with a total floor area of 2250 m2 (24,200 ft2) and a window-to-wall ratio of 0.2 with a floor-to-floor height of 3.66 m (12 ft), broken up between a 2.74 m (9 ft) occupied floor and a 0.92 m (3 ft) plenum per floor. The building also included a single elevator shaft.
The internal gains for the occupied spaces were divided into three parts: lighting, receptacle loads and occupants. The thermostats operated on a setpoint with setback/setup basis. The heating setpoint was 21.1 °C (70 °F) with a setback temperature of 12.8 °C (55 °F) and the cooling setpoint was 23.9 °C (75 °F) with a setup temperature of 32.2 °C (90 °F).
The HVAC system included water-source heat pumps (WSHPs) with a cooling tower and a boiler serving the common loop. Each zone had its own WSHP rejecting/extracting heat from the common loop. The outdoor air for each zone was supplied to each individual heat pump, and the heat pump blower was on at all times when the zone was occupied. When the location of the building required an economizer, the outdoor air controls were applied to the individual heat pump’s airflow. With this approach, different heat pumps could have a different percentage of outdoor air at the same time depending on the loads. Three of the modeled locations included economizers and two did not. Return airflow was specified to equal 95 percent of supply airflow.
The results showed that reducing the air leakage rate to the target level by including a continuous air barrier system resulted in an average reduction in infiltration of 83 percent. The economic impact is shown in Table 1 below:
Table 1 Energy cost savings for office building[iii]
City
Gas Savings
Electrical Savings
Total Savings
Bismarck
$1,854 (42%)
$1,340 (26%)
$3,195
Minneapolis
$1,872 (43%)
$1,811 (33%)
$3,683
St. Louis
$1,460 (57%)
$1,555 (28%)
$3,016
Phoenix
$124 (77%)
$620 (9%)
$745
Miami
$0 (0%)
$769 (10%)
$769
Note: The full report, Investigation of the Impact of Commercial Building Envelope Airtightness on HVAC Energy Use, is available for download from the NIST website at www.nist.gov
What makes an air barrier?
Air barrier systems must be constructed of materials with an air permeance rating of less than 0.004 cfm/ft2 (0.2 L/sm2 at 75 Pa) when tested at their intended-use thickness in accordance with ASTM E 2178. They must be continuous throughout the building envelope with interconnected, flexible joints[iv]. The air barrier must be able to withstand positive and negative air pressures without displacement and must be durable enough to last the life of the building.
Of course, all penetrations in the air barrier must be sealed or the assembly itself becomes leaky, which defeats the purpose of installing the system in the first place.
The Air Barrier Association of America (ABAA) has published Master Specifications for several different air barrier materials and systems that meet the performance requirements of state and model Energy Codes on its website: www.airbarrier.org.
One of the most frequently specified air barrier materials is closed-cell spray-applied polyurethane foam. This is because in addition to providing an air permeance rating of less than 0.001 L/s/m2at an application thickness of 1.5 inches, the material also offers an effective insulation R-value of over 6 per inch and in many states also qualifies as a vapor barrier. Spray-applied polyurethane foam is a two-component product manufactured on site but engineered in the molecular level to meet required performance criteria for every code and climate.
Spray-applied and seamless, it conforms to any shape, fully-adheres to the wall system and requires no fasteners, thereby eliminating thermal bridging, convection loss behind insulation boards, and condensing surfaces, while also increasing installation speed and reducing labor costs. It can also improve structural strength, according to testing conducted by the National Association of Home Builders (NAHB) Research Center[v].
For the future
Although the idea of mandating air barrier systems for new commercial construction is a relatively new phenomenon in the United States, Canada has included air barriers in its National Building Code for over two decades. In recent years, Massachusetts, Wisconsin and Michigan have begun mandating air barrier systems as part of their Commercial Energy Codes. Although air barrier systems are now required by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE’s) Advanced Energy Design Guide: Small Office Buildings, and the New Building Institute’s BenchmarkTM for Advanced Buildings, for the first time, continuous air barrier systems may become a requirement by the ASHRAE under Addendum z to Standard 90.1-2004, Energy Standard for Buildings Except Low-Rise Residential Buildings; at the time of writing, this Addendum was in public review.
Architects and Professional Engineers designing and specifying materials and mechanical systems in non-residential buildings can improve performance by understanding the impact of uncontrolled air leakage and the role of the air barrier system in optimizing building energy efficiency and durability, as well as occupant comfort, health and safety. To this end, the Air Barrier Association of America provides training programs for architects, specifiers and engineers, as well as a certified installer program with third-party quality control inspections to ensure correct installation of the systems.
Additional Resources on the Air Barrier and its Impact on HVAC Performance:
The National Institute of Standards and Technology (NIST) www.nist.gov
[ii]Air Barrier Systems in Buildings, Anis, Wagdy AIA, Whole Building Design Guide, www.wbdg.org , a program of the National Institute of Building Sciences (NIBS)
[iii]Investigation of the Impact of Commercial Building Envelope Airtightness on HVAC Energy Use, Emmerich, Steven J. (Building and Fire Research Laboratory, NIST), McDowell, Timothy P. (TESS Inc.) and Anis, Wagdy AIA (Shepley Bulfinch Richardson and Abbott),
[iv]Commissioning the Air Barrier System, Anis, Wagdy, AIA, ASHRAE Journal, March 2005.
[v]Evaluation Report 12932-R, Canadian Construction Materials Centre (CCMC), National Research Council (NRC) of Canada.